Monitoring a compressed air refrigeration dryer is paramount for maximizing energy efficiency, safeguarding product quality, preventing machinery damage, identifying necessary maintenance, and achieving substantial cost savings. This ensures the seamless operation of compressed air systems across various industrial applications.
With our continuous advancements in sensor technology and evaluation electronics, we deliver heightened precision under diverse ambient temperatures and enhanced signal resolution. Like their predecessors, our new dew point sensors promise enduring stability and reliable measurement results. Designed to resist condensation and shielded from contamination by a stainless-steel sintered cap, these sensors stand as a testament to our commitment to excellence.
Expert Recommendation:
Mounting with a standard measuring chamber for compressed air systems up to 16 bar
Unmatched Advantages:
Effortless installation with quick coupling
Special Attributes:
• Exceptionally long-term stability
• Analog output ranging 4...20 mA for precise dew point measurements
• Superior condensation resistance
• Rapid adaptation time
• Pressure resistance up to 350 bar (special version)
• NEW: Advanced Modbus-RTU interface for enhanced communication
• NEW: Superior resolution of sensor signals thanks to upgraded evaluation electronics
• NEW: On-site sensor diagnostics with portable devices or CS Service Software
Comprehensive Data via Modbus:
TECHNICAL DATA: FA 510/515
Measuring range | -80…20 °Ctd, -20…50 °Ctd |
Accuracy | ± 1 °C at 50…-20 °Ctd ± 2 °C at -20…-50 °Ctd ± 3 °C at -50…-80 °Ctd |
Pressure range | -1…50 bar Special version up to 500 bar |
Power supply | 24 VDC (10…36 VDC) |
Protection class | IP 66 |
EMC | In acc. with DIN EN 61326-1 |
Operating temperature | -20…70 °C |
Connection | M12, 5-pin |
PC connection | 4…20 mA = -80…20 °Ctd 4…20 mA = -20…50 °Ctd FA 510: 4…20 mA (3-wire) FA 515: 4…20 mA (2-wire) |
Burden for analogue output | < 500 Ω |
Screw-in thread | G 1/2″ Stainless steel Optional: UNF 5/8", NPT 1/2" |
Dimensions | Ø 30 mm, length approx. 130 mm |
Choose units | % RH, °Ctd, g/m³, mg/m³, ppm V/V |
Scaling | 4…20 mA change |