Introducing the XJK-LG5C Xinjian LCD Display Refrigerated Air Dryer Controller
Manufactured by Hangzhou Xinjian Electronic Co., Ltd., this controller is designed for precise refrigeration control. Made of durable cast iron, it is both customizable and a standard component. Ensure optimal performance and efficiency with this reliable and high-quality product.
Introducing our LCD display compressor air dryer controller and Refrigerated air dryer controller. With an LCD display, every temperature can be easily programmed. This multi-function controller supports two languages and can detect and display pressure and dew point. Enhance your air dryer system with our advanced controllers.
Function: |
|
Set |
Contain 4 buttons to set. |
Display |
128x32 LCD and 7 pcs of LED lights to show alarm information. |
Temp. detect |
detect and display 4 channels of temperature (inlet gas, outlet gas, condensation, evaporation). |
Temp. offset |
Offset of each temp. can be programmed to avoid error |
Analog signal |
4-20mA current signal x2, pressure and dew point |
Language |
Chinese / English |
Compressor reduce-voltage start |
switch time will be take before start compressor Delay certain time before restart compressor, each time can be re-programmed |
Fan control |
Control fan motor based on condensing temperature |
Auto drain |
Control the work of drain valve based on preset value. |
Compressor protect |
Start protect: delay certain time when start compressor Alarm protect: stop compressor when has overload alarm, high pressure alarm, low pressure alarm signal. |
Dew point control |
Control compressor based on dew point |
Alarm |
N.O signal x1, output alarm signal via relay |
Communication |
Supply monitor software free, Modus profile, use RS485 interface. |
Remote /local |
Can choose different control mode, remote control or local control |
Link |
Can be controlled by outer link signal |
Subordinate start |
Output a start signal for subordinate machine after compressor work |
Performance Indices: |
|
Type |
XJK-LG5C |
Rating voltage |
AC 220V 50Hz |
Temp. detect range |
0- 90°C |
Temperature precision |
± 1°C |
Temp. sensor |
NTC |
Pressure/dew point signal |
4-20 mA |
Output |
8 x dry contact via relay (N.O.) |
Output capacity |
5A @250VAC |
Box size |
215x145x105 |