Introducing the unparalleled FA 500, your ultimate choice for dew point measurement. This advanced instrument comes with an integrated display and alarm relay, designed specifically for refrigeration, membrane, and adsorption dryers.
Readable via Modbus:
- Pressure dew point [°Ctd.]
- Temperature [°C]
- Relative humidity [% RH]
- Absolute humidity [g/m³]
- Degree of humidity [g/m³]
- Moisture content V/V [ppmV/V]
- Water vapor partial pressure [hPa]
- Atmospheric dew point [°Ctd.atm]
TECHNICAL DATA FA 510/515
Measuring range | -80…20 °Ctd, -60… 30 °Ctd, -20…50 °Ctd, or 0…100% RH |
Accuracy | ± 1 °C at 50…-20 °Ctd ± 2 °C at -20…-50 °Ctd ± 3 °C at -50…-80 °Ctd |
Pressure range | -1…50 bar Special version up to 500 bar |
Power supply | 24 VDC (10…36 VDC) |
Protection class | IP 65 |
EMC | In acc. with DIN EN 61326-1 |
Operating temperature | -20…50 °C |
Connection | 2 x M12, 5-pin for analogue output, Modbus-RTU and alarm output, M-Bus (optional) Ethernet (PoE) (optional) |
PC connection | 4…20 mA = -80…20 °Ctd 4…20 mA = -60…30 °Ctd 4…20 mA = -20…50 °Ctd |
Burden for analogue output | < 500 Ω |
Alarm relay | NC, max. 60 VDC, 0.5 A |
Screw-in thread | G 1/2″ |
Dimensions housing | 76.5 x 85 x 75 mm (WxHxD) |